Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/16/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) THE TWO NITE LITES NL ON PLAN REQUIRE BATTERY BACKUP. PLEASE RETRO FIT BATT.PAK. 2.) THE EMERGENCY WALL PACKS, THE NIGHT LITES, AND TEH EXIT SIGNS SHOULD BE ON A SEPARATE CIRCUIT TO PREVENT TURN OFF WHICH WOULD RESULT IN BATTERY DISCHARGE AND FAILURE OF EMERGENCY FEATURE. CONSULT WITH ENGINEER FOR DIRECTION. THANKS. |