Permit: T02CM02337

Parcel: 132191140

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM02337

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/16/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) THE TWO NITE LITES NL ON PLAN REQUIRE BATTERY BACKUP. PLEASE RETRO FIT BATT.PAK. 2.) THE EMERGENCY WALL PACKS, THE NIGHT LITES, AND TEH EXIT SIGNS SHOULD BE ON A SEPARATE CIRCUIT TO PREVENT TURN OFF WHICH WOULD RESULT IN BATTERY DISCHARGE AND FAILURE OF EMERGENCY FEATURE. CONSULT WITH ENGINEER FOR DIRECTION. THANKS.