Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T02CM02337

Parcel: 132191140

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/30/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/29/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245* 1.) PLASTIC TY-RAPS ARE NOT APPROVED TO SUPPORT M.C CABLE OR CONDUIT. 2.) INSTALL SEPARATE TIE WIRES FOR SUPPORT OF CONDUIT AND SUPPORT OF M.C. CABLE. 3.) REMOVE THE SNAKE WRAPS OF M.C. CABLE TO EMT. ADD SUPPROT WIRES. 4.) REMOVE "SNAKE" WRAPS OF FIXTURE AND J' BOX 1 OUTLET BOX WIRE FROM MC CABLE ADD SUPPORT WIRES FOR THE M C CABLE SUPPORT WIRE MUST BE TIED TO GRID, SO AS TO BE TAUT SEE ART 300 NEC & ART 334 FOR MC CABLE USE ONLY APPROVED STRAPS TO SUPPORT CONDUIT. THANKS.