Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM02337
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/29/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1.) PLASTIC TY-RAPS ARE NOT APPROVED TO SUPPORT M.C CABLE OR CONDUIT. 2.) INSTALL SEPARATE TIE WIRES FOR SUPPORT OF CONDUIT AND SUPPORT OF M.C. CABLE. 3.) REMOVE THE SNAKE WRAPS OF M.C. CABLE TO EMT. ADD SUPPROT WIRES. 4.) REMOVE "SNAKE" WRAPS OF FIXTURE AND J' BOX 1 OUTLET BOX WIRE FROM MC CABLE ADD SUPPORT WIRES FOR THE M C CABLE SUPPORT WIRE MUST BE TIED TO GRID, SO AS TO BE TAUT SEE ART 300 NEC & ART 334 FOR MC CABLE USE ONLY APPROVED STRAPS TO SUPPORT CONDUIT. THANKS. |