Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*ELECT ABOVE CEILING APPROVED. |
| 09/25/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) OK LOCATIONS OF EQUIP. IN BASEMENT. 2.) INSTALL INSULATED BUSHINGS ON CONNECTORS FOR CONDUCTORS #4 AWG AND LARGER PER 300-4 NEC. 3.) MUST HAVE 36" IN FRONT AND 30" HORIZONTAL WORKING CLEARANCE IN FRONT OF DISC. SWITCHES ON ROOF. 110-26. NEC. |