Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM02316
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*ELECT ABOVE CEILING APPROVED. | |
09/25/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) OK LOCATIONS OF EQUIP. IN BASEMENT. 2.) INSTALL INSULATED BUSHINGS ON CONNECTORS FOR CONDUCTORS #4 AWG AND LARGER PER 300-4 NEC. 3.) MUST HAVE 36" IN FRONT AND 30" HORIZONTAL WORKING CLEARANCE IN FRONT OF DISC. SWITCHES ON ROOF. 110-26. NEC. |