Permit: T02CM02316

Parcel: 125091980

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/17/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*ELECT ABOVE CEILING APPROVED.
09/25/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) OK LOCATIONS OF EQUIP. IN BASEMENT. 2.) INSTALL INSULATED BUSHINGS ON CONNECTORS FOR CONDUCTORS #4 AWG AND LARGER PER 300-4 NEC. 3.) MUST HAVE 36" IN FRONT AND 30" HORIZONTAL WORKING CLEARANCE IN FRONT OF DISC. SWITCHES ON ROOF. 110-26. NEC.