Inspection History: ELECTRIC - FINAL
Permit Number - T02CM02315
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK C OF O. | |
| 06/03/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) NO REVISED PLAN SHOWING LIGHTING AND NEW RECEPTACLE INSTALLATIONS FOR EXAM ROOMS. 2.) NO ABOVE CEILING APPROVAL, ABOVE CEILING WAS NOT CALLED IN PRIOR TO COVERING BRANCH CIRCUIT WIRING FOR FANS, OUTLETS HOME RUNS BACK TO PANEL. | |
| 05/31/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES 1.) NO LIGHT FIXTURES IN EXAM ROOMS. 2.) NO EXIT LIGHTS PER PLAN SEE SHEET T-1. 3.) NO ABOVE CEILING INSPECTION APPROVAL. 4.) PLANS NEED TO REFLECT LIGHTING INSTALLATION IN EXAM ROOMS, ALSO ELECTRICAL OUTLET MODIFICATION. 5.) RE DUNDENT GROUNDED BRANCH CIRCUITS TO BE CONTINUEOUS TO BREAKER PANEL. |