Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/21/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLBG FINAL IS OK
2.) OK FOR C OF O.
11/19/2002 PLUMBING - FINAL Denied 1.) FLEX CONNECTOR CAN ONLY BE 3'-0" FROM GAS VALVE TO REGULATOR.
2.) MUST SCREEN DOWN FLU VENTS WITH (3) SHEET METAL SCREWS PER JOINT @ WATER HTRS.
3.) WATER HTRS REQUIRE EXPANSION TANKS DUE TO CLOSED SYSTEM BY P.R.V.
4.) MUST PROVIDE PERM SCREW CAPS FOR C.O.
5.) MUST CAULK WATER CLOSETS.