Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/10/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 06/06/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0920*NO ACCESS TO BLDG. |
| 06/05/2002 |
MECHANICAL - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*DUCT SMOKE DETECTORS GO IN THE RETURN NOT SUPPLY. FLEX DUCT IS REQUIRED TO HAVE MIN 1 1/2" WIDE HANGER STRAP. NOT 1". TERMINATE CONDENSATE INTO A 1" FITTING DO NOT REDUCE. |