Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM02304
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
06/06/2002 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0920*NO ACCESS TO BLDG. | |
06/05/2002 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*DUCT SMOKE DETECTORS GO IN THE RETURN NOT SUPPLY. FLEX DUCT IS REQUIRED TO HAVE MIN 1 1/2" WIDE HANGER STRAP. NOT 1". TERMINATE CONDENSATE INTO A 1" FITTING DO NOT REDUCE. |