Permit: T02CM02304

Parcel: 124120270


Addresses:

1100 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM02304

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
06/06/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0920*NO ACCESS TO BLDG.
06/05/2002 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*DUCT SMOKE DETECTORS GO IN THE RETURN NOT SUPPLY. FLEX DUCT IS REQUIRED TO HAVE MIN 1 1/2" WIDE HANGER STRAP. NOT 1". TERMINATE CONDENSATE INTO A 1" FITTING DO NOT REDUCE.