Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM02296
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
09/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) SEAL OFF IN COLUMN FOR CANOPY LIGHTING IS NOT FILLED 2) SEAL OFF NOT WITHIN 18" FROM EXP. PROOF PUMP AND COUPLING IN BETWEEN SEALL OF AND PUMP ARE NOT EXP. PROOF 3) SEALING COMPOUND TO BE UTILIZED IN UNUSED SEALS OFF |