Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2002 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 9/15/02 AT 9:15AM. OK TO CLEAR. | |
| 11/06/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000* | |
| 11/06/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0215*1.) REPAIR THE TOP PLATES ABOVE THE HALLWAY 4 GANG SWITCH BOX. DO NOT NAIL DRAW THE TOP PLATES BECAUSE CABLES WILL BE PINCHED TO TIGHTLY. 2.) RELOCATE THE SMOKE DETECTOR TO THE HALLWAY CIEILING OR WALL. KEEP 3 FEET AWAY FROM RETURN AIR DUCT REGISTER. 3.) USE SMOOTH 'J' HOOK STRAPS OR OTHER APPROVED STRAPS TO SUPPORT THE SER CABLE IN ATTIC AND AT WALL SPACE DOWN TO THE METER CAN. 4.) DO NOT USE ROMEX SCRAPS OR SHEALTH FOR CABLE SUPPORT. 5.) SOME OUTLET BOXES ARE CROOKED OR OUT OF WALL. REPAIR. 6.) DOOR BELL TRANSFORMER SHOULD NOT BE LOCATED IN CLOTHES. KEEP LOW VOLTAGE CABLE OUT OF HIGH VOLTAGE BOX. RECALL WHEN CORRECTED THANKS. |