Permit: T02CM02293

Parcel: 134082980

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/05/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP ON 9/15/02 AT 9:15AM. OK TO CLEAR.
11/06/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*
11/06/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*1.) REPAIR THE TOP PLATES ABOVE THE HALLWAY 4 GANG SWITCH BOX. DO NOT NAIL DRAW THE TOP PLATES BECAUSE CABLES WILL BE PINCHED TO TIGHTLY.
2.) RELOCATE THE SMOKE DETECTOR TO THE HALLWAY CIEILING OR WALL. KEEP 3 FEET AWAY FROM RETURN AIR DUCT REGISTER. 3.) USE SMOOTH 'J' HOOK STRAPS OR OTHER APPROVED STRAPS TO SUPPORT THE SER CABLE IN ATTIC AND AT WALL SPACE DOWN TO THE METER CAN.
4.) DO NOT USE ROMEX SCRAPS OR SHEALTH FOR CABLE SUPPORT.
5.) SOME OUTLET BOXES ARE CROOKED OR OUT OF WALL. REPAIR.
6.) DOOR BELL TRANSFORMER SHOULD NOT BE LOCATED IN CLOTHES. KEEP LOW VOLTAGE CABLE OUT OF HIGH VOLTAGE BOX. RECALL WHEN CORRECTED THANKS.