Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM02291

Parcel: 134082970

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/05/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
11/06/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*REMOVE MAIN PANEL COVERS FOR THIS INSPECTION. CORRECTION: 1.) RELOCATED SMOKE DETECTOR TO HALLWAY CIELING OR WALL KEEP 3' AWAY FROM RETURN AIR DUCT. 2.) 4 GANG SWITCH BOX IS SET CROOKED IN WALL & OTHER BOXES CROOKED. 3.) SUPPORT CABLES ABOVE LAUNDRY ROOM. 4.) DO NOT INSTALLED DOOR BELL TRANSFORMER IN CLOTHES CLOSET. 5.) DO NOT INSTALL DOOR BELL TRANSFORMER IN CLOTHES CLOSET. 6.) DO NOT PLACE LOW VOLTAGE DB. WIRES IN HIGH VOLT BOX. 7.) USE APPROVED SMOOTH "J HOOK" OR OTHER STRAPS ON PNL. FEEDER SER CABLE. PUT 2 X 4 SUPPORTS IN FRONT OF CABLE AND STRAP CORRECTLY AT METER PANEL WALL. 8.) REMOVE PAPER FROM INTERIOR OF RECESSED CAN LITES.