Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*REMOVE MAIN PANEL COVERS FOR THIS INSPECTION. CORRECTION: 1.) RELOCATED SMOKE DETECTOR TO HALLWAY CIELING OR WALL KEEP 3' AWAY FROM RETURN AIR DUCT. 2.) 4 GANG SWITCH BOX IS SET CROOKED IN WALL & OTHER BOXES CROOKED. 3.) SUPPORT CABLES ABOVE LAUNDRY ROOM. 4.) DO NOT INSTALLED DOOR BELL TRANSFORMER IN CLOTHES CLOSET. 5.) DO NOT INSTALL DOOR BELL TRANSFORMER IN CLOTHES CLOSET. 6.) DO NOT PLACE LOW VOLTAGE DB. WIRES IN HIGH VOLT BOX. 7.) USE APPROVED SMOOTH "J HOOK" OR OTHER STRAPS ON PNL. FEEDER SER CABLE. PUT 2 X 4 SUPPORTS IN FRONT OF CABLE AND STRAP CORRECTLY AT METER PANEL WALL. 8.) REMOVE PAPER FROM INTERIOR OF RECESSED CAN LITES. |