Permit: T02CM02239

Parcel: 121063180


Addresses:

5521 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/17/2002 FRAMING Approved
10/10/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*
08/20/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SHIM HEADERS WHERE NEEDED 2) FINISH SECURING FIREPLACE TO FRAME 3) STIFFIN STUD IN FIREPLACE ANGLE WALL-NEXT TO DOOR 4) INSTALL RED HEADS IN PLATE-EAST FAMILY ROOM WALL 5) BLOCK DUCT BOOTS WHERE NEEDED 6) FINISH PRE-WIRE OF BED CEILING LIGHTS 7) CORRECT EAST HALL BATH VENT FAN LOCATION 8) FINISH DRYER DUCT INSTALL AT ROOF AND FLOOR
08/16/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) SERVICE PANEL RISER NOT COMPLETE PUT TEMP ADDRESS ON PANEL 2) ALL TRADES NOT COMPLETED