Permit: T02CM02214

Parcel: 133142300

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/23/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/20/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) SUPPORT MC WITHIN 12" PER NEC EACH TERMINATION. 2.) LIGHT FIXTURE IN DRIVE THRU CEILING MISSING FLEX FITTING. 3.) DO NOT SUPPORT MC TO EMT CONDUIT, MUST BE SUPPORTED TO STRUCTURE.
09/19/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*NOTES 1.) OK WALLS INSIDE TELLER OFFICE 2.) MC CABLE MUST BE SUPPORTED WITHIN 12" EACH TERMINATION PER NEC. 3.) INSTALL GROUND RODS BOND TO BLD. STEEL PER 1 LINE DIA. SEE SHEET ON PLAN E3-1. 4.) EXPOSED PVC MUST BE SCH 80.
08/05/2002 ELECTRIC - INTERMEDIATE Partial Approval OK SERVICE INSTALL NEED BOND POSTED AND APPROVAL OF OTHER INSPECTORS. SEE FORM.