Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 09/03/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0950*/ 1) 1/DT1 NOT COMPLIED WITH 2) NORTH AND WEST WALLS COVERED WITHOUT APPROVAL REMOVE 3) PROVIDE EPOXY SPECIAL INSPECTION REPORTS FOR HOLDOWNS 4) HOLDOWN BOLTS LOOSE 5) STOPPED INSPECTION |
| 07/18/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0160*/ 1) POST BASES AND POST CAPS MISSING THROUGHOUT 2) 25/S-3 NOT COMPLIED WITH-REQUEST ARCHITECT CLARIFICATION 3) 5 1/2 X 15 GLUE LAM BEAL ON ? WHERE IS 3 1/8 X 10 1/2 POST ? 3) #3 HOLDOWNS NOT IN 4) PORCH NOT ON 5) PLAN CALLS FOR WALL TO BE PER 10/DT1 AT REAR-SHOULD BE 6/DT2-REVISE PLAN HOUSE NOT BUILT PER ANY DETAIL 6) HOUSE NOT BUILT PER PLAN |