Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/30/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 08/22/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0935*/ 1) 4 EACH DOUBLE 2 X POSTS AT GARAGE MISSING 2) GARAGE SHEAR WALL ANCHOR BOLTS MISSING 3) POST CAPS NOT NAILED 4) HOLDOWNS NOT IN 5) SEVERAL POSTS MISSING ON BEARING SHEARWALL 6) HOUSE WRAPPED WITHOUT APPROVAL-REMOVE 7) HAVE FRAME SUPERINTENDENT VERIFY HOUSE BUILT TO PLAN PRIOR TO NEXT INSPECTION ALL FUTURE FAILURES WILL BE CHARGED RE-INSPECTION FEES 8) TO MANY ITEMS STOPPED INSPECTION, REFEE CHARGED FOR LATH INSTALLATION WITHOUT APPROVAL |
| 08/13/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO WATER TEST ON SEWER AND VENT LINES, NO WATER TEST ON SUPPLY LINES 2) UNIT WRAPPED IN FOAM COULD NOT FIND CLIP AND SHEATHING APPROVAL 3) AIR DUCT TO BEDROOM #3 CLOSET NOT BLOCKED ON 3 SIDES |
| 07/26/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) POST BASES AND CAPS NOT INSTALLED 2) 25/S3 NOT COMPLIED WITH 3) GARAGE TRIMMERS NOT CLIPPED 4) 6/DT2 REQUIRES LEDGER BLOCKED AND NAILER 5) CORNER NOT SUPPORTED AT 2ND FLOOR 6) STRAPS AND CLIPS MISSING THROUGHOUT |
| 07/18/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0160*/ 1) HOUSE NOT BUILT PER PLAN SEE ITEMS FROM PERMIT #T02CM02204 |