Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/07/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INSTALL DEAD FRONT ON SUB PANEL 2) IDENTIFY ALL CIRCUITS IN BOTH PANELS 3) ELECTRIC PANELS NOT BONDED UFER MISSING, PROVIDE 2 8' GROUND RODS AT 6' APART, GAS/WATER AND PANEL NOT BONDED 4) SEAL TOP OF SOUTH EAST CORNER FROM NEW CONSTRUCTION TO EXISTING HOUSE |