Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM02180
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS OK TO INSTALL. DAMPER AND ANGLE IRON OK FOR CEILING TILES. | |
06/25/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) PROVIDE MIN 1/4" CLEARANCE AROUND FIRE DAMPERS. 2.) NEED TO SEE FIRE DAMPER OPENINGS. PROVIDE APPROVED ACCESS DOORS FOR FIRE DAMPERS. 3.) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN SYSTEM AS PER 2000 IMC. 4.) NEED TO SEE EXISTING DAMPER CAPPED OFFICE CORRIDOR 114. 5.) PROVIDE CONDENSATE DRAINS AS PER PLANS OK TO PROCEED W/GRID. |