Permit: T02CM02180

Parcel: 11101035B


Addresses:

3800 E RIVER RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM02180

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2002 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS OK TO INSTALL. DAMPER AND ANGLE IRON OK FOR CEILING TILES.
06/25/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PROVIDE MIN 1/4" CLEARANCE AROUND FIRE DAMPERS. 2.) NEED TO SEE FIRE DAMPER OPENINGS. PROVIDE APPROVED ACCESS DOORS FOR FIRE DAMPERS. 3.) PROVIDE DUCT SMOKE DETECTORS IN THE RETURN SYSTEM AS PER 2000 IMC. 4.) NEED TO SEE EXISTING DAMPER CAPPED OFFICE CORRIDOR 114. 5.) PROVIDE CONDENSATE DRAINS AS PER PLANS OK TO PROCEED W/GRID.