Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 06/26/2003 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 12/19/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR, IRC 3507.2 2) INSTALL TWO EACH 8' GROUND RODS 6' APART CONNECTED TO SECOND BUILDING SUB PANEL PER IRC SECTION 3507.3 AND 35073.1, UNDERGROUND CONDUIT OK TO COVER |