Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM02175
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*ALL ELECTRIC WIRING HAS BEEN REMOVED OK FINAL. | |
05/10/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) WE HAVE METER CONTRACT. PLEASE INSTALL SPLIT BOLT AS PER MANUFACTURE INSTRUCTIONS. 2.) RAMPS NOT COMPLETED AREA NOT TO BE USED FO ROCCUPANCY AT THIS TIME. | |
05/09/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) SPLIT BOLTS TO BE LISTED FOR ALUMINIUM WIRING 110-3. 2.) INSULATION FOR TAP CONNECTION TO BE EQUAL MANFACTURES INSULATION 110-14. 3.) PROVIDE PROTECTION FOR CONDUITS EXPOSED ACCROSS ASPHALT. | |
05/08/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PLEASE SUPPORT CONDUIT AT POLE WITH RIGID SUPPORTS AS DISCUSSED. 2.) PLEASE TEMPORARY LABEL BREAKER USED FOR FEEDING AREA AND SUBPANEL BREAKERS. 3.) WE NEED TO OPEN UP A FEW POINTS ALONG UNDERGROUND RUN. 4.) CONDUIT HAS SEPERATED AT JUNCTION BOX. 5.) CONDUIT TO BE SCH 80 ALONG TOP OF WITH ARAMP FOR PROTECTION. 6.) SUPPORT CONDUITS ABOVE GROUND AT TRAILER. 7.) THE METAL TENT FRAME SHOULD BE BONDED TO THE SERVICE TO PREVENT DIFFERENCE IN POTENTIAL. 8.)SUPPORT SEALITE AS PER CODE. 9.) BOXES FOR RECEPTACLES NEED RIDGID SUPPORT NOT TY-RAPS. 10.) PLEASE SUPPORT EXIT AND EMERGENCY LIGHTS EFFECTIVELY. 11.) USE AN APPROVED FITTING FOR LB CHASE NIPPLE IS NOT APPROVED 12.) FILL UNUSED OPENINGS AT PANEL. 13.) BACKED BREAKER NEEDS MAUFACTURE HOLD DOWN DEVICE. |