Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM02173
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
09/04/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) SHEARWALL 2 AT LIVING ROOM REQUIRES ANCHOR BOLTS AND EDGE BLOCKS 2) END FLOOR EXTERIOR SILL PLATE MUST BE NAILED W/2-16D AT 12" ON CENTER AND BEARING WALL 3) BLOCK AND NAIL #1 SHEAR PANELS AND FLOOR PER PLAN | |
08/23/2002 | FRAMING | Denied | IVRS - Inspection 0950*/ 1) ELECTRIC NOT COMPLETE ENOUGH TO INSPECT 2) DUCT Y'S AND TRANSITIONS MUST BE INSULATED R-6 MINIMUM 3) DUCTS RESTRICTED THROUGHOUT-MINIMUM BEND RADIUS=1 DUCT DIAMETER MINIMUM 4) DUCTS BOOT S BENT AT CONNECTION 5) STOPPED INSPECTION TO MANY ITEMS |