Permit: T02CM02173

Parcel: 112021240

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM02173

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2002 FRAMING Approved IVRS - Inspection 0000*
09/04/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) SHEARWALL 2 AT LIVING ROOM REQUIRES ANCHOR BOLTS AND EDGE BLOCKS 2) END FLOOR EXTERIOR SILL PLATE MUST BE NAILED W/2-16D AT 12" ON CENTER AND BEARING WALL 3) BLOCK AND NAIL #1 SHEAR PANELS AND FLOOR PER PLAN
08/23/2002 FRAMING Denied IVRS - Inspection 0950*/ 1) ELECTRIC NOT COMPLETE ENOUGH TO INSPECT 2) DUCT Y'S AND TRANSITIONS MUST BE INSULATED R-6 MINIMUM 3) DUCTS RESTRICTED THROUGHOUT-MINIMUM BEND RADIUS=1 DUCT DIAMETER MINIMUM 4) DUCTS BOOT S BENT AT CONNECTION 5) STOPPED INSPECTION TO MANY ITEMS