Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM02173
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
08/13/2002 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) SOUTH SIDE GARAGE FRONT #3 SHEAR PANEL MUST EXTEND FROM HOLDOWN TO HOLDOWN ONE BROKEN 2) GARAGE SOUTH WEST CORNER #1 SHEAR APNEL REQUIRES 1/2" AB WITHIN 12" OF PLATE END 3) EAST 6060 WINDOW RACKED 4) OSB ROOF SHEATHING MUST SPAN 2 BAYS, (3 TRUSSES) REPLACE ALL SHORT PANELS 5) TECO TESTED OSB ROOF SHEATHIN IS DELAMINATING. HAVE A WOOD PRODUCTS ENGINEER PROVIDE A WRITTEN CERTIFICATION MEETING REQUIRED STANDARDS DUT TO EXPOSURE TO WEATHER 6) ROOF SHEATHING NOT SUPPORTED ON ONE EDGE ABOVE BATH AT VAULT |