Permit: T02CM02172

Parcel: 110065940

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T02CM02172

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2002 FRAMING Approved IVRS - Inspection 0000*
07/08/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) NO GAS TEST 2) GAS LINE NOT COMPLETE 3) PRVOIDE CPI INSTRUCTIONS FOR INSTALLATION AT INTERIOR BEARING WALL 4) PROVIDE GFCI OUTLET FOR DOUBLE LAVATORY
07/03/2002 FRAMING Denied IVRS - Inspection 0950*1.)HOLD DOWNS NOT NAILED. 2.) WIRES MUST HAVE 1/4" SHEATHING IN BOXES 3.) NO MECHANICAL CONDENSATE DRAIN. 4.) LEAK ON 1" PEX 5.) TWO HOLD DOWNS BOLTS NOT EPOXIED 6.) DONT RESTRUCTED AT PLENIUM BY GAS LINE 7.) GAS LINE NOT PROPERLY SUPPORTED