Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM02168
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
02/12/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*CRIMP ON DRYER VENT MUST RUN THE SAME DIRECTION AS AIR FLOW. RECALL FOR INSPECTION. | |
11/25/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*HAVE YOUR PLUMBING INSPECTOR CHECK WATER PIPING ON ROOF FOR BOILER. FINISH CONNECTING MAKE UP AIR UNIT & EXHAUST FAN. PROVIDE SCREWS IN WATER HEATER VENT & BOILER VENT. FINISH INSTALLING DRYER VENT. ARCHITECT SENT REVISION FOR MECHANICAL CHNAGES IN MAINTENANCE SHOP. OK FOR TEMP C OF O. |
|
11/21/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*ALL MECHANICAL HAS BEEN ELIMINATED FROM MAINTENANCE AREA. HAVE YOUR ENGINEER OR ARCHITECT DELETE FROM PLANS. PROVIDE DRYER VENT AS PER PLANS. FINISH INSTALLING BOILER VENT. VENT HOOD MISSING FROM WATER HEATER. FINISH HOOD UP OF UNIT ON ROOF LOWER TRAP ON AC UNIT. PAINT EXPOSED PVC W/LATEX PAINT. LABEL DATA PLATE W/PROPER HEAT KIT INSTALLED & FUSE UNIT ACCORDINGLY. |