Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2002 |
PLUMBING - YARD WTR LINE/TEST |
|
Approved |
|
| 10/01/2002 |
PLUMBING - YARD WTR LINE/TEST |
|
Partial Approval |
IVRS - Inspection 0000*1.) WATER LINE HAS 12" OF CLEARANCE FROM BOTTOM OF BLDG. SEWER. 2.) OK TO BACKFILL TRENCH. 3.) MUST SEE FINAL CONNECTION TO BLDG. SERVICE. |
| 09/27/2002 |
PLUMBING - YARD WTR LINE/TEST |
|
Denied |
IVRS - Inspection 0999*1.) MUST HAVE MIN 12" OF CLEARANCE FROM TOP OF WATER LINE TO BOTTOM OF BLDG. SEWER AS REQUESTED. 2.) MUST PAY REINSPECTION FEE BEFORE NEXT INSPECTION. |
| 09/26/2002 |
PLUMBING - YARD WTR LINE/TEST |
|
Not ready for Inspection |
IVRS - Inspection 0000*NOT READY FOR INSPECTION. |
| 09/25/2002 |
PLUMBING - YARD WTR LINE/TEST |
|
Denied |
IVRS - Inspection 0999*1.) MUST HAVE MIN 12" OF SEPARATION OF BLDG. SEWER AS REQUESTED 2.) DO NOT COVER. |