Permit: T02CM02168

Parcel: 133201280


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T02CM02168

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2002 PLUMBING - YARD WTR LINE/TEST Approved
10/01/2002 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) WATER LINE HAS 12" OF CLEARANCE FROM BOTTOM OF BLDG. SEWER. 2.) OK TO BACKFILL TRENCH. 3.) MUST SEE FINAL CONNECTION TO BLDG. SERVICE.
09/27/2002 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) MUST HAVE MIN 12" OF CLEARANCE FROM TOP OF WATER LINE TO BOTTOM OF BLDG. SEWER AS REQUESTED. 2.) MUST PAY REINSPECTION FEE BEFORE NEXT INSPECTION.
09/26/2002 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection 0000*NOT READY FOR INSPECTION.
09/25/2002 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) MUST HAVE MIN 12" OF SEPARATION OF BLDG. SEWER AS REQUESTED 2.) DO NOT COVER.