Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM02159
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
06/18/2002 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) ELECTRIC OUTLETS REQUIRED WITHIN 6 FEET OF DOOR WAYS AND EVERY 12 FEET THERE AFTER 2 EACH MISSING IN LIVING ROOM 2) WIRES KINKED AT BATHROOM OUTLETS MUST HAVE 5 DIAMETER BEND RADIUS | |
06/13/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) LOOSE ANCHOR BOLTS THROUGHOUT HOUSE 2) ELECTRICAL BOXES WIRES NOT ROUGHED IN 3) PROTECT ALL ELECTRICAL WIRES WITHIN 1 1/4" FROM EDGE OF STUD 4) WATER HEATER TEMP PRV MUST GO TO DAY LIGHT DRAINING INTO WASHER TAIL PIPE NOT AN APPROVED FITTING, MAY APPEAL TO THE BUILDING OFFICIAL AT DSD CITY OF TUCSON 5) PROVIDE APPROVED TRUSS DRAWING 6) STRAP PATIO BEAM INSIDE AND AD 2 X STUDS 2 EACH 7) 2 X 4 OUTRIGGERS 4' ON CENTER NOT INSTALLED 8) REPLACE KING STUD AT KITCHEN WINDOW | |
05/31/2002 | FRAMING | Denied | IVRS - Inspection 0925*/ 1) NOT READY UNTIL ALL INTERMEDIATES ARE COMPLETE |