Permit: T02CM02131

Parcel: 141305990

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T02CM02131

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
07/17/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
07/15/2002 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) WEST SIDE, CARRY VERTICAL SUPPORT FROM GIRDER ALL THE WAY DOWN TO FOUNDATION ( BOTH ENDS OF GIRDER) TO HAVE VERTICAL SUPPORT 2) MISSING HORIZONTAL NAILING INTERIOR SHEAR AT STAIR 3) BLOCK UNDER JOINT IN FLOOR SHEATHING FRONT BEDROOMS 3) MISSING HORIZONTAL NAILING FRONT SHEAR 4) MISSING H2.5 AT FRONT WALL TRUSS TO TOP PLATE 5) CAN FIND NAIL SIZE USED IN TRUSS TO GIRDER HANGER 6) ONE PIECE OF OSB TURNED THE WRONG WAY BLOCK AT JOINT MAIN ROOF NEAR RIDGE WEST SIDE 7) AT GARAGE P-3 SHEAR TO BE CONTINOUS UP/TO G-4 SHEAR 8) INTERIOR SHEAR AT STAIRS REQUIRES SHEAR CONNECTION, PANELS TOP OF SHEAR TO ROOF, NAIL AT ROOF DECK
07/10/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) LOOSE ROOF PANELS ALL AREAS 2) SHEARWALLS INTERSECTIONS NOT PER DETAIL 10/SD4 OR 11/SD4 3) BACK WALL 1ST FLOOR REQUIRES 12" ON CENTER FRAMING (SEE SHEET S2) 4) CHECK ALL DETAILS FOR COMPLIANCE BEFORE RECALL