Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM02131
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2002 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
07/15/2002 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) WEST SIDE, CARRY VERTICAL SUPPORT FROM GIRDER ALL THE WAY DOWN TO FOUNDATION ( BOTH ENDS OF GIRDER) TO HAVE VERTICAL SUPPORT 2) MISSING HORIZONTAL NAILING INTERIOR SHEAR AT STAIR 3) BLOCK UNDER JOINT IN FLOOR SHEATHING FRONT BEDROOMS 3) MISSING HORIZONTAL NAILING FRONT SHEAR 4) MISSING H2.5 AT FRONT WALL TRUSS TO TOP PLATE 5) CAN FIND NAIL SIZE USED IN TRUSS TO GIRDER HANGER 6) ONE PIECE OF OSB TURNED THE WRONG WAY BLOCK AT JOINT MAIN ROOF NEAR RIDGE WEST SIDE 7) AT GARAGE P-3 SHEAR TO BE CONTINOUS UP/TO G-4 SHEAR 8) INTERIOR SHEAR AT STAIRS REQUIRES SHEAR CONNECTION, PANELS TOP OF SHEAR TO ROOF, NAIL AT ROOF DECK | |