Permit: T02CM02114


Addresses:

4410 S PARK AV


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM02114

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
05/22/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) NOTES: 1) COMPLETE INSTALL OF CAN LTS AND 2 X 4 LAY IN FIXTURES IN BREIFING ROOM 2) A/C DISCONNECTS OUTSIDE BLDG, NOT IN WORKING CLEANCE COMPLIANCE. NEED 36" IN FRONT, 30" HORIZONTAL PER 110-2+6 NEC 3) OK CEILING IN HOLDING CELL RECEIVEING ROOM
05/21/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
04/17/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*