Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 05/22/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NOTES: 1) COMPLETE INSTALL OF CAN LTS AND 2 X 4 LAY IN FIXTURES IN BREIFING ROOM 2) A/C DISCONNECTS OUTSIDE BLDG, NOT IN WORKING CLEANCE COMPLIANCE. NEED 36" IN FRONT, 30" HORIZONTAL PER 110-2+6 NEC 3) OK CEILING IN HOLDING CELL RECEIVEING ROOM |
| 05/21/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/17/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |