Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM02114
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
05/22/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) NOTES: 1) COMPLETE INSTALL OF CAN LTS AND 2 X 4 LAY IN FIXTURES IN BREIFING ROOM 2) A/C DISCONNECTS OUTSIDE BLDG, NOT IN WORKING CLEANCE COMPLIANCE. NEED 36" IN FRONT, 30" HORIZONTAL PER 110-2+6 NEC 3) OK CEILING IN HOLDING CELL RECEIVEING ROOM | |
05/21/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
04/17/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000* |