Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T02CM02107
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2002 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
06/17/2002 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection 0999*1.)RE FASTEN INSULATION WHERE IT HAS DROPPED OUT OF ROOF CAVITIES. 2.) CIELING GRID DOES NOT MEET CISCA INSTALLATION STANDARDS NOR UBC INSTALLATION STANDARDS. IE: CISCA DOES NOT NOT ALLOW POP RIVETS FOR ALIGNMENT PURPOSES. THE CIELING NEEDS TO FLOAT IN PLACE: OR UBC ALLOWS POP RIVETS BUT YOU MUST USE HANGERS WITHIN 8" OF PERIMETER ON ALL MAIN AND CROSS RUNNERS. |