Permit: T02CM02107

Parcel: 13701007U


Addresses:

5580 S NOGALES HY

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
06/20/2002 BUILDING ABOVE CEILING Approved IVRS - Inspection 0000*
06/17/2002 BUILDING ABOVE CEILING Denied IVRS - Inspection 0999*1.)RE FASTEN INSULATION WHERE IT HAS DROPPED OUT OF ROOF CAVITIES. 2.) CIELING GRID DOES NOT MEET CISCA INSTALLATION STANDARDS NOR UBC INSTALLATION STANDARDS. IE: CISCA DOES NOT NOT ALLOW POP RIVETS FOR ALIGNMENT PURPOSES. THE CIELING NEEDS TO FLOAT IN PLACE: OR UBC ALLOWS POP RIVETS BUT YOU MUST USE HANGERS WITHIN 8" OF PERIMETER ON ALL MAIN AND CROSS RUNNERS.