Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/27/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/21/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FLEX NOT ALLOWED FOR PRV AT WATER HEATER NEED HARD PIPE 2) CONDENSATE LINE NEEDS TO BE PAINTED 3) FORCED AIR UNIT OVER FUSED 4) VENTS NEED TO BE 10 FEET AWAY FROM UNIT OR TWO FEET ABOVE 5) DISHWASHER DRAIN LINE NEEDS TO BE ABOVE THE FLOOD RIM |
| 01/13/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CANNOT HAVE ELECTRIC OUTLET UNDER KITCHEN OVER HANG COUNTER TOP 2) POST PERMANENT ADDRESS NUMBERS ON HOUSE 3) COMPLETE GRADING STOP AWAY FROM HOUSE 4) COMPLETE PLUMBING BATH VANITIES 5) CUT SEWER CLEAN OUTS TO GRADE 6) SEAL AROUND HOSE BIB CONNECTIONS EXTERIOR 7) BREAK OFF LOCK ON ANTI-SIPHON 8) MINIMUM 3" CLEARANCE WATER HEATER PTR LINE TERMINATION EXTERIOR 9) GAS PIPE REAR PORCH NOT ON PLANS 10) INSTALL RECEPTACLE COVERS ALL OUTLETS, SWITCHES, ETC... 11) NEED TO UNLOCK STORAGE ROOM FOR INSPECTION |