Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T02CM02086
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000*INSPECTED FIRE DAMPERS. HOOK UP ELECTRICAL, FIRE CAULK AROUND ANGLES AS NEEDED. PROVIDE ACCESS DOORS. WILL CHECK ON FINAL. OK FOR CEILING TILES. | |
09/23/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTIONS ON ROOMS 132,134,135,140,142,152,174. OK FOR CIELING TILES. | |
09/18/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*INSPECTED 5 FIRE DAMPER OPENING IN AREAS 144,137,132. OK TO INSTALL DAMPERS & ANGLES. WILL CHECK ACCESS DOORS ON NEXT INSPECTION. | |
08/19/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*PLENUIM ABOVE GRID WATER LINE INSUL NEEDS FLAME/SMOKE RATING. 1.) FIRE CAULK RETAINING ANGLE, FIRE DAMPER AT. 2.) EXAM RM. #162 OPEN PENETRATION NEEDS FIRE DAMPER IN OPENING. 3.) DOORWAY #172 NEEDS TO SEAL OPENING ABOVE FIRE DAMPER. | |
08/13/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*FIRE DAMPER PENETRATION OK. PROCEED W/ INSERTION OF SLEEVES, ONE SIDE W/RETAINING ANGELS ONLY. | |
06/26/2002 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* INSPECTED FIRE DAMPER OPENING IN HALL 172 OK TO PROCEED. FLEX DUCT IN OFFICE 180 PROVIDE MORE SUPPORT. OK FOR CEILING TILES IN AREA 175,173,176, 178, 180,181,179,164,165,167,182. |