Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 06/03/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH RUN TO BUILDING FOR CARPORT LIGHTS 2) WE HAVE EXPOSED CONDUCTORS IN DRYWALL BETWEEN BATH LIGHT AND WALL 3) IF BOX IS BACK FROM SURFACE 1/4" OR MORE AN APPROVED EXTENDER RING IS NEEDED. 370-20 ALSO ON ROOF 4) LABEL A/C DISCONNECTING MEANS 5) TIGHTEN LOOSE SEAL TIE FITTINGS |