Permit: T02CM02051

Parcel: 117081150


Addresses:

848 S 7TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/04/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*FIRE DAMPERS, RM #113 OK EXIST SOUTH END, NEW DOWN FROM ROOF, OK TO COVER.
11/25/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*AIR HANDLERS WILL BE ABOVE TO BE REMOVED MOVE ELECTRICAL NOW.
2.) FIRE DAMPERS PROGRESSING TO BACK OF CORRIDOR WALL BEING COVERED? IMC LIGHT FIXTURE IN ATTIC 306.3. 306.3 PASSAGE WAY AND PLATFORM IF NECESSARY.
11/13/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*CLEAR ACCESS PANELS AT AIR HANDLERS IN TRUSSES. A/H MUST FIT THROUGH ACCESS OPENING IF REPLACING IS NECESSARY.
PROVIDE LIGHTS AT A/H PANELS FOR SERVICE AS PER IMC
TWO 2 COMB. SMOKE FIRE DAMP. PROGRESSING RM. 113. OK TEMP POWER FOR TESTING.
10/29/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*CHECKED ROUGH DUCT ABOVE HARD LIDS. OK TO SHEET ROCK ALL CEILINGS EXCEPT ROOM 113,120,119, & NEW SECTION & CORRIDOR STILL NEED TO SEE FINAL/SMOKE DAMPERS.
10/23/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*HAVE YOUR ENGINEER RE-DESIGN FIRE DAMPER OPENING IN STORAGE ROOM CEILING. CHECKED DUCT ABOVE CEILINGS SOUTH HALF OF BLDG. PROVIDE BACKING AROUND CEILING BOXES. OK TO COVER CEILING SOUTH HALF. NEED TO CHECK AIR HANDLER ABOVE DECK.