Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2002 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000*FIRE DAMPERS, RM #113 OK EXIST SOUTH END, NEW DOWN FROM ROOF, OK TO COVER. | |
| 11/25/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*AIR HANDLERS WILL BE ABOVE TO BE REMOVED MOVE ELECTRICAL NOW. 2.) FIRE DAMPERS PROGRESSING TO BACK OF CORRIDOR WALL BEING COVERED? IMC LIGHT FIXTURE IN ATTIC 306.3. 306.3 PASSAGE WAY AND PLATFORM IF NECESSARY. |
|
| 11/13/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*CLEAR ACCESS PANELS AT AIR HANDLERS IN TRUSSES. A/H MUST FIT THROUGH ACCESS OPENING IF REPLACING IS NECESSARY. PROVIDE LIGHTS AT A/H PANELS FOR SERVICE AS PER IMC TWO 2 COMB. SMOKE FIRE DAMP. PROGRESSING RM. 113. OK TEMP POWER FOR TESTING. |
|
| 10/29/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*CHECKED ROUGH DUCT ABOVE HARD LIDS. OK TO SHEET ROCK ALL CEILINGS EXCEPT ROOM 113,120,119, & NEW SECTION & CORRIDOR STILL NEED TO SEE FINAL/SMOKE DAMPERS. | |
| 10/23/2002 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*HAVE YOUR ENGINEER RE-DESIGN FIRE DAMPER OPENING IN STORAGE ROOM CEILING. CHECKED DUCT ABOVE CEILINGS SOUTH HALF OF BLDG. PROVIDE BACKING AROUND CEILING BOXES. OK TO COVER CEILING SOUTH HALF. NEED TO CHECK AIR HANDLER ABOVE DECK. |