Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK C OF O. | |
| 12/17/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*NOTES OK FOR TEMP C OF O TO MOVE IN FURNITURE. 1.) COMPLETE INSTALLATION OF EXIT LTS, PANEL SCHEDULE. LABELS, CHANGE OUT CONDENSER DISCONNECTS. |
|
| 12/10/2002 | ELECTRIC - FINAL | Not ready for Inspection | NOTES AC CONDENSING UNITS #3,4,5,6, RUN WITH #10 CU. AWG FROM LOAD CENTER MUST HAVE MAX 30 OVERCURRENT PROTECTION PER 310-16 TABLE. SEE ALSO 240-3. |