Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* OK FINAL |
| 06/20/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE PROVIDE A LETTER AURTHURIZING USE OF M/C CABLE PLANS CALL FOR CONDUIT. 2.) SUPPORT FLEX CONDUIT AS PER CODE. 3.) PLANS ARE NOT REFLECTIVE OF WORK INSTALLED PLEASE REVISE PLANS OR INSTALL AS PER PLANS. |