Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T02CM02045
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2003 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000*SENT TO TEP ON 3/18/03 AT 9:15AM OK TO CLEAR OK TO METER #1 TEC CABLE DROP FOR BOTH UNITS OK. | |
| 03/13/2003 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0210* 1.) To quality for this inspection you must have a GFI receptacle (or one fed from a GFI circuit breaker) Located below the panel load center. 2.) The service riser conduit must be fitted with a bonding bushing. The bushing must be grounded to the neutral bar. 3.) The ground rod clamp msut be raised to near the top of the rod. This is so that the connections will be readily inspectable always. |