Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T02CM02045

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2003 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*SENT TO TEP ON 3/18/03 AT 9:15AM OK TO CLEAR OK TO METER #1 TEC CABLE DROP FOR BOTH UNITS OK.
03/13/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0210*
1.) To quality for this inspection you must have a GFI receptacle (or one fed from a GFI circuit breaker) Located below the panel load center.
2.) The service riser conduit must be fitted with a bonding bushing. The bushing must be grounded to the neutral bar.
3.) The ground rod clamp msut be raised to near the top of the rod. This is so that the connections will be readily inspectable always.