Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2002 |
FRAMING |
|
Approved |
|
| 04/17/2002 |
FRAMING |
|
Denied |
1) NEED TRUSS SPECS AND ADDITIONAL DETAILS (SHEET SD2) ? 2) STUD TO TERMINATE AT SPLIT OF BOTTOM PLATES 3) CHECK ALL HEADER SIZES 4) ALL REJECTED ITEMS NOT COVERED |
| 04/12/2002 |
FRAMING |
|
Denied |
1)INSTALL ALTERNATE HOLDOWN WHERE MAS NOT NIALED ONTO STUD (SINGLE GARAGE) 2) STUD MISSING OVER BEARING HEADER BATHROOM 3) FILL SOLIDLY ALL HEADERS AT BEARING4) FIREBLOCK MISSING UNTO STAIRWELL AND BEHIND WASHER BOX 5) INSTALL SOLID WOOD 1ST TO 2ND FLOOR AT GIRDER TRUSS BEARING POINTS 6) AT LEDGE SPLICE USE DOUBLE STUDS AND STRAP LEDGER WITH C320 X18" STRAP 7) IF TRUSS SPAN13'-1" TO 15'-0" INSTALL A35 EACH STUD TO LEDGER 8)BEDROOM STUD WAY OUT OF PLUMBING UPSTAIRS 9) SECURE RETURN AIR PLENIUM TO TRUSSES. |