Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTION. | |
| 12/26/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE FINISH #1-5 PREVIOUS INSPECTION. 2.) AN APPROVED EXTENDER RING IS NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE METAL ARE NOT APPROVED. |
|
| 12/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*OK WALL AT UTILITY ROOM. 1.) MAINTAIN WORKING CLEARENCE IN FRONT OF PANEL "B" DELI 2.) NEED ACCESS TO CONNECTIONS AT FLORAL CASE 3.) SECURE JUNCTION BOX DELI COOLER 4.) WE HAVE MULTIPOLE LOOSE FITTING UNDER CAKE COOLER AND MISSING JUNCTION BOX COVERS 5.) TIGHTEN LOOSE FITTINGS UNDER CASH REGISTRAR. 6.) PVC GLUE IS NEEDED FOR FITTINGS UNDER DELI CASE AND LOOSE FITTINGS. |
|
| 10/23/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK FOR TEMP C OF O FOR PHARMACY. | |
| 10/16/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) CORRECTLY INSTALL BOX UNDER FLOOR COOLER USE AN APPROVED FITTING AND MAIN CONDUIT CONTINUITY OF RUN. 2.) LIGHTS BY DAIRY CASE TO BE SUPPROTED 3.) SUPPORT M/C CABLE AS PER CODES 334 & 300-11. 4.) SUPPORT DATA ABOVE GRID FRONT BACK TO DAIRY AREA. OK TEMP C OF O. PHARMACY & WALK IN COOLER SUBJECT TO OTHER INSPECTORS AND POSTING OF BOND. | |
| 10/15/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) AN EXTENDER RING IS NEEDED WHERE THE BOX AND DEVICE ARE MORE THAN 1/8" SEPERATION 2.) WE HAVE EXPOSED CONDUCTOR PLEASE CLOSE JUNCTION BOX. 3.) WATER HEATER TO HAVE DISCONNECTING MEANS. 4.) DATA TO BE SUPPORTED CORRECTLY NOT LAID ACCROSS PIPES. 5.) PLEASE CORRECT GROUNDING. 6.) JUNCTION BOX COVERS AT FLOOR COVERS. 7.) SECURE AND MAKE SAFE RECEPTACLES BY WALK IN DOOR 8.) SEAL ALL ENTRANCE TO WALK IN FOR MOISTURE. NOTE A BOND WILL BE NEEDED FOR TEMP C OF O TO OPERATE. |