Permit: T02CM01923

Parcel: 11918036A


Addresses:

600 W AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM01923

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/24/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) ROMEX WHICH RUNG THUR METAL STUD TO EX FAN NEED RED BUSHING. 2.) #2 ABOVE STATES ALL ROMEX TO BE SUPPORTED OR STRAPPED WITH IN 12" OF BOXES. 3.) INSTALL A ROMEX CONNECTOR ON RECEPTACLE BOX ON EAST WALL WHERE RUN INTO BOX. 4.) TIE ALL NEUTRALS AND GROUNDS TOGETHER IN BOXES. ALL OF THESE ITEMS COME UNDER FIRST STATEMENT RUN ROMEX CORRECTELY. 5.) WAS A ROMEX CONNECTOR USED TO TIE ROMEX INTO FAN.
07/18/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*DENIED ROMEX RUN INCORRECTLY. 1.) ROMEX HAS TO BE SUPPORTED WITH IN 12" OF EVERY BOX. 2.) ROMEX THUR METAL STUDS REQUIRES GROMETS INSTALLED ON STUD HOLES PLASTIC FOR ROMEX. TO PASS THUR. 3.) ROMEX TO WALL RECEPTACLE INCORRECTLY BROUGHT OUT OF METAL STUD AND SPACE IN MOTOR OR BRICK JOINT HAS TO BE 1 1/4" DEEP.