Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/09/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/24/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) ROMEX WHICH RUNG THUR METAL STUD TO EX FAN NEED RED BUSHING. 2.) #2 ABOVE STATES ALL ROMEX TO BE SUPPORTED OR STRAPPED WITH IN 12" OF BOXES. 3.) INSTALL A ROMEX CONNECTOR ON RECEPTACLE BOX ON EAST WALL WHERE RUN INTO BOX. 4.) TIE ALL NEUTRALS AND GROUNDS TOGETHER IN BOXES. ALL OF THESE ITEMS COME UNDER FIRST STATEMENT RUN ROMEX CORRECTELY. 5.) WAS A ROMEX CONNECTOR USED TO TIE ROMEX INTO FAN. |
| 07/18/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*DENIED ROMEX RUN INCORRECTLY. 1.) ROMEX HAS TO BE SUPPORTED WITH IN 12" OF EVERY BOX. 2.) ROMEX THUR METAL STUDS REQUIRES GROMETS INSTALLED ON STUD HOLES PLASTIC FOR ROMEX. TO PASS THUR. 3.) ROMEX TO WALL RECEPTACLE INCORRECTLY BROUGHT OUT OF METAL STUD AND SPACE IN MOTOR OR BRICK JOINT HAS TO BE 1 1/4" DEEP. |