Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T02CM01915
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2002 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
04/30/2002 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) CANNOT USE 3" VENT PIPE ON A 4" FAN OUTLET. PROVIDE 4" AND PROVIDE THE BACKDRAFT DAMPERS THAT CAME WITH THE FANS. 2.) ON FINAL PROVIDE ON OUTSIDE AIR VENT ON AC UNIT. MARK DATA PLATE ON UNIT W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3.) TERMINATE CONDENSATE INTO AN APPROVED LOCATION VENT ON TRAP SHOULD BE DOWNSTREAM OF TRAP. |