Permit: T02CM01915

Parcel: 12202001A


Addresses:

4604 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM01915

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*OK FOR C OF O.
04/30/2002 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999* 1.) CANNOT USE 3" VENT PIPE ON A 4" FAN OUTLET. PROVIDE 4" AND PROVIDE THE BACKDRAFT DAMPERS THAT CAME WITH THE FANS. 2.) ON FINAL PROVIDE ON OUTSIDE AIR VENT ON AC UNIT. MARK DATA PLATE ON UNIT W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3.) TERMINATE CONDENSATE INTO AN APPROVED LOCATION VENT ON TRAP SHOULD BE DOWNSTREAM OF TRAP.