Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2002 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. |
| 04/30/2002 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* 1.) CANNOT USE 3" VENT PIPE ON A 4" FAN OUTLET. PROVIDE 4" AND PROVIDE THE BACKDRAFT DAMPERS THAT CAME WITH THE FANS. 2.) ON FINAL PROVIDE ON OUTSIDE AIR VENT ON AC UNIT. MARK DATA PLATE ON UNIT W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3.) TERMINATE CONDENSATE INTO AN APPROVED LOCATION VENT ON TRAP SHOULD BE DOWNSTREAM OF TRAP. |