Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/02/2002 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OVERHEAD WATER DISTIBUTION IS OK 4.) OK FOR DRYWALL & CONCRETE. |
| 04/30/2002 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON SYSTEM ALL THE WAY TO TOP OF VENT THRU ROOF. 2.) CAN ONLY SEWER 2 FIXTURES ON 1/2" COLD SUPPLY. 3.) CAN NOT FLAT VENT WATER CLOSET AND FLOOR DRAIN. THIS ROUGH SOIL WAS CONNECTED TO EXSISTING TRAP ARM FOR EXSISTING WATER CLOSET. 4.) MUST PROVIDE 1/2" GROMETS OR ISOLATORS ON ALL COPPER LINES THAT PASSES THROUGH METAL STUDS. 5.) MUST USE SPECIALTY COUPLING ON REVENTS. 6.) MUST STRAP DOWN WATER DISTRIBUTION. 7.) CONNECT TRAP PRIMER. |