Permit: T02CM01905

Parcel: 123150770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM01905

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL SUBJECT TO OTHER INSPECTIONS
1.) FINISH #3 & #5 PREVIOUS INSPECTION.
12/18/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) WHAT IS NEW CIRCUIT RUN INTO PANEL AFTER INSPECTION FOR ROUGH ELECTRIC. A CONNECTOR IS NEEDED ALSO
2.) USE AN APPROVED FOR GROUNDING BATH FIXTURES.
3.) USE CORRECT SIZED GROUNDING EQUIPMENT CONDUCTORS TO A/C UNITS.
4.) CORRECLY IDENTIFY UNGROUNDING CONDUCTORS IN WATER HEATER DISCONNECT AND GROUNDING CONDUCTORS.
5.) PROTECT BULB IN CLOSET.
6.) #8 NM CABLE AMPACITY ONLY 40 AMPS 336-26.
7.) LOOSE FLEX FITTING AT WATER HEATER.