Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 09/20/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 09/19/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0220*CONNECT GROUNDING ELECTRODE TO NEUTRAL (GROUNDING) TERMANAL NOT GROUNDING TERMANAL. A REFEE MAY BE ASSESSED IF THIS IN NOT DONE. |
| 09/16/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*1.) FINISH ITEM #3. OF PREVIOUS INSPECTION. 2.) SERVICES TO BE ADDRESS AS JOB CARD. |
| 09/11/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
PROVIDE A LEVEL SPACE IN FRONT OF SERVICES AS PER CODE 110-26. 2.) FILL UNUSED OPENINGS AT SERVICE 3.) GROUNDING ELECTRODE CONDUCTOR TO BE ATTACHED AT GROUNDED TERMANAL 250-24. 4.) CANNOT USE SHEET METAL SCREWS FOR GROUNDING 250-8. 5.) CLEAN SURFACE UNDER LUG 250-12. 6.) GFI TO BE ON EXTERIOR OF STRUCTURE. 7.) PLEASE HAVE JOB CARD ON SITE. ADDRESS DO NOT MATCH. |