Permit: T02CM01905

Parcel: 123150770

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T02CM01905

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
09/19/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0220*CONNECT GROUNDING ELECTRODE TO NEUTRAL (GROUNDING) TERMANAL NOT GROUNDING TERMANAL. A REFEE MAY BE ASSESSED IF THIS IN NOT DONE.
09/16/2002 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection 0000*1.) FINISH ITEM #3. OF PREVIOUS INSPECTION. 2.) SERVICES TO BE ADDRESS AS JOB CARD.
09/11/2002 ELECTRIC - CABLE DROP Denied PROVIDE A LEVEL SPACE IN FRONT OF SERVICES AS PER CODE 110-26. 2.) FILL UNUSED OPENINGS AT SERVICE 3.) GROUNDING ELECTRODE CONDUCTOR TO BE ATTACHED AT GROUNDED TERMANAL 250-24. 4.) CANNOT USE SHEET METAL SCREWS FOR GROUNDING 250-8. 5.) CLEAN SURFACE UNDER LUG 250-12. 6.) GFI TO BE ON EXTERIOR OF STRUCTURE. 7.) PLEASE HAVE JOB CARD ON SITE. ADDRESS DO NOT MATCH.