Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM01905
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK ROUGH ELECTRIC. | |
10/08/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PLEASE VERIFY CABLE CONNECTOR LISTING FOR NUMBER OF CABLES IN EACH CONNECTOR. 2.) FINISH ITEMS #2 & 5 OF PREVIOUS INSPECTION. | |
10/02/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) INSTALL CABLE IN CONNECTOR AS PER LISTING FOR USEAGE 2.) WE HAVE OVER FILL IN BOXS 3.) MAINTAIN FIRE WALL SEPERATION AND PENITRATIONS. 4.) SUPPORT NM CABLE WITH IN 12" OF BOX OR FITTING. 5.) PROTECT CONDUCTOR IN BOXES 370-43. |