Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T02CM01900
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2002 | PLUMBING - SEWER HCS CONNECT | Approved | ||
08/12/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*1.) FINAL RUN BETWEEN MANHOLES OK WATER TEST FROM LOWEST TO HIGHEST POINT OK OK TO COVER 2.) NEED TO SEE TIE -INS FROM BUILDING DRAIN TO BLDG SEWER. | |
08/09/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*1.) 5# AIR TEST FROM MANHOLE TO MANHOLE OK 2.) WILL WATER TEST FINAL SECTION. | |
08/08/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*1.) GREASE TRAP OK OK TO COVER 2.) BLDG SEWER COMPLETE WITH TWO MANHOLES FINAL APPROVAL SUBJECT TO AIR TEST AND VERIFICATION OF GRADE 3.) GAS PRESSURE TEST OK. | |
08/07/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000* | |
08/02/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*8" SDR AS NOTED ON PLAN OK TO COVER TEST AT A LATER DATE REQUIRE VERIFICATION OF GRADE BEFORE FINAL.. | |
07/12/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000*NOT READY FOR INSPECTION. | |
07/10/2002 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999*1.) CONTRACTOR SECTION 103.5.4. REQUIRES THAT THE WORK BE READY BEFORE CALLING IN INSPECTION. | |
07/09/2002 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000* | |
07/01/2002 | PLUMBING - SEWER HCS CONNECT | Partial Approval | 1.) N/H UNDERGROUND IN KITCHEN AREA, INCLUDING DRAIN FOR GREASE TRAP, AND VENT FOR SAME OK WATER TEST ONE RISER TO TEN FEET OK 2.) OK TO COVER KITCHEN TO TWO WAY CLEAN OUT. NEED TO SEE GREASE TRAP. 3.) OK AS NOTED ON PLAN. |