Permit: T02CM01876

Parcel: 123023980


Addresses:

2872 E VESPERS PL

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
07/10/2002 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000* OK CABLE DROP ONLY, NO POWER YET CABLE DROP APPROVAL TO ALLOW FOR TRENCH BACKFILL SEE ATTACHED FORM FOR TEMP POWER.
07/09/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245* NOTES 1.) ADDRESS LABEL MUST BE SCREWED OR RIVITED TO ENCLOSURE 230-70 NEC. #9287 CITY ORD. 2.) BOND BUSHING REQUIRED ON RISER CONDUIT PER 250-94 NEC. 3.) RISER SUPPORT NOT STRONG ENOUGH, USE 1/4" MIN. BOLTS TO SECURE.
07/03/2002 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0215*NO RISER CONDUIT.