Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* OK CABLE DROP ONLY, NO POWER YET CABLE DROP APPROVAL TO ALLOW FOR TRENCH BACKFILL SEE ATTACHED FORM FOR TEMP POWER. |
| 07/09/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245* NOTES 1.) ADDRESS LABEL MUST BE SCREWED OR RIVITED TO ENCLOSURE 230-70 NEC. #9287 CITY ORD. 2.) BOND BUSHING REQUIRED ON RISER CONDUIT PER 250-94 NEC. 3.) RISER SUPPORT NOT STRONG ENOUGH, USE 1/4" MIN. BOLTS TO SECURE. |
| 07/03/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*NO RISER CONDUIT. |