Permit: T02CM01876

Parcel: 123023980


Addresses:

2872 E VESPERS PL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/29/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/06/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*ARCH. TO SUBMIT LETTER FOR USE OF ALUM CONDUCTORS FOR SUB-PANEL FEEDER OK INTER, SUBJECT TO RECEIPT OF LETTER FROM ARCH OF CHANGE TO ALUM. FEEDER TO SUB PANEL.
06/05/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) PUSH IN GROMMETS NOT ALLOWED AS ROMEX TERMINATION INTO METAL BOXES FOR WALL LIGHTS, ROMEX MUST BE SECURED TO BOX. 370-17 NEC. 2.) USE APPROVED METHOD TO TERMINATE CABLE INTO RANGE RECEPT BOXES, HOLE DRILLED IN PLASTIC BOX NOT APPROVED, 110-3 NEC 110-12. 3.) CAT #5 CABLE NOT AN APPROVED METHOD TO SUPPORT FEEDER ROMEX HOME RUNS INTO PANELS ART 336,110-12,370-17,110-3 NEC. 4.) PLANS INDICATE 150 AMP. PANELS. 5.) ALL CONDUCTORS TO BE COPPER.