Permit: T02CM01852

Parcel: 115071900


Addresses:

33 W LEE ST #01


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T02CM01852

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2003 PLUMBING - INTERMEDIATE Approved CLOSET FLANGES OK
05/04/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) CORRECTIONS MADE OK
2.) ABS DWV OK WATER TEST OK
3.) PEX WATER OK
4.) CLOSET FLANGES NEED TO SEE BEFORE FINAL TABS OK.
OK TO COVER WALLS.
05/01/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) ALL PLUMBING MUST BE EXPOSED REMOVE INSULATION WHERE REQUIRED.
2.) AGGREGATE CROSS SECTIONAL AERA OF VENTING TO EQUAL LARGEST REQUIRED BLDG. SEWER.
3.) INSTALL PER PLAN AND RETEST.
04/30/2003 PLUMBING - INTERMEDIATE Denied NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED REMOVE ALL INSULATION COVERING ANY PLUMBING FOR INSPECTION.
2.) REQUIRE WATER TEST ABS.
04/28/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING MAY NOT HAVE HORIZONTAL PIPING EXCEPT FOR TRAP ARM. NOTE: THE WET VENTED SECTION IS BETWEEN THE WATER CLOSET AND THE LAVATORY.
2.) USE OF A COMBO ON A TRAP ARM AT KITCHEN SINK, PUTS THE WEIR OF THE TRAP ABOVE THE POINT OF VENT (CAN CAUSE SIPHONAGE) USE A SANTEE ON DRAINAGE PIPING (TRAP ARM) USE A COMBO AS A CLEAN OUT EXTENSION.
04/22/2003 PLUMBING - INTERMEDIATE Denied 1.) A TRAP ARM MAY NOT CHANGE SIZE A TRAP IS TO BE THE SAME SIZE AS THE TRAP ARM A TRAP MAY BE ONLY ONE PIPE SIZE LARGER THAN THE TAILPIECE TO WHICH IT IS CONNECTED.
2.) HORIZONTAL X HORIZONTAL CHANGE FO DIRECTION TO BE THRU WYE BRANCH OR EQUIVILENT.
3.) NEED TO FILL DWV SYSTEM WITH WATER OR AIR.