Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM01852
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
04/28/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*MAKE UP ALL WIRING IN BOXES. CHECK YOUR STAPLEING. | |
04/22/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1.) STAPLE ROMEX WITHIN 12" EACH TERMINATION. PER NEC. 336. 2.) USE LISTED ROMEX CONNECTORS AT PANELS. GROUPED CABLES THRU 1 1/2" BUSHING NOT ALLOWED. PER NEC. 370-17. 3.) CHECK MULTI GANG BOXES FOR OVERFILL IN CONDUCTOR CAPACITY 370-16. 4.) PLANS MUST BE ON SITE. |