Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/20/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/19/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEXT FAILURE WILL BE CHARGED A RE-INSPECTION FEE 2) BLOCKING FOR DRYWALL SHEAR MISSING IN GARAGE WEST WALL-7 FEET 2) FIRE BLOCK EAST BEDROOM FURRED OUT WALL 3) ITEM 6 FROM PRIOR INSPECTIONS NOT COMPLIED WITH |
| 06/11/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE BLOCKING FOR TOP PLATE DRYWALL SHEARWALL NAILING 2) NAIL PROTECT PLUMBING WITHIN 1 14/" OF STUD SURFACE 3) NO GAS PRESSURE TEST 4) HALL BATH WATER CLOSET DOES NOT HAVE 15" CLEARANCE TO TUB 5) FIRE BLOCK BEDROOM WINDOW DEAD SPACE 6) FIRE BLOCK LEDGER WALLS BELOW BOTTOM CHORD OF TRUSSES 7) BAD PEX CONNECTION ABOVE RANGE DUCTS RESTRICTED |
| 05/31/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GARAGE SHEARWALL 1 ABOVE DORP CEILING OSB OK |