Permit: T02CM01844

Parcel: 104092180


Addresses:

4151 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02CM01844

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*RECEIVED ALL PAPERWORK FOR FINAL.
01/08/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH ITEMS #1 & 6 PREVIOUS INSPECTION.
01/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) PLEASE VERIFY LISTINGS FOR RADIAL ARM, SAW, LEVELOR MACHINE (#2).
2.) FINISH STRAPING M/C CABLE AT CASHIER STATIONS AND COUNTERS (#1)
3.) SUPPORT CHANDLER BY BOX NOT EARS (#8).
4.) FILL UNUSED OPENINGS IN MOLD TRACK AT FNA & CHANDLER DISPLAYS (#11).
5.) REPAIR BROKEN M/C AT MANUFACTURED CORD END DOORS COUNTER (#16).
6.) PROVIDE LETTER FOR ELECTED ELECTRICAL(#6)
*ROPE CUTTER TO BE REMOVED.
12/17/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) TIGHTEN LOOSE FITTING AT SENSORMATIC BOXES.
2.) FILL UNUSED OPENINGS
3.) MAINTAIN WORKING CLEARENCE IN FRONT OF SWITCH BOARD.
2.) FILL UNUSED OPENING
3.) MAINTAIN WORKING CLEARENCES IN FRONT OF SWITCH
12/16/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) SUPPORT MANUFACTURED WIRING SYSTEM WITH IN 12" OF BOX OR FITTING 334 & 10.
2.) PLEASE VERIFY LISTING FOR ROPE CUTTERS, LEVOLOR MACHINE, DISPENSER
3.) PLESE VERIFY LOADS TO BUSS CIRCUITS AND HOW RACKS ARE CIRCUITED.
4.) FIINISH SUPPORTING MANFACTURED PAPER WORK FOR CORD CONNECTED LIGHT FIXTURES TO CHECK LISTING.
6.) PROVIDE A LETTER REGARDING ALL DELETED ELECTRICAL
7.) LABEL BRAKERS AT BUSS WAY.
8.) SUPPORT CHANDLER BOX BY THE BOX NOT THE EARS.
9.) SUPPORT CONDUIT AS PER CODE ABOVE SWITCHING NORTH END APPL. TEST OUTLETS.
10.) GROUND APPL. TEST OUTLETS
11.) FILL UNUNSED OPENINGS IN CHANDLER DISPLAY. FAN DISPLAY
12.) WALL OF WINDOWS DISPLAY MISSING FIXTURE END CAP.
13.) PROPERLY INSTALL CORD CAP AT WALL OF WINDOW DISPLAY.
14.) EXTENTION CORDS NOT BE USE AS PERMANENT WIRING METHOD OR ANY CORD FROM FIXTURE TO OUTLETS.
15.) LIGHT DISPLAY CORD TO BE SECURED TO JUNCTION BOX WITH CONNECTORS AS PERVIOUSLY DISCUSSED.
16.) REPAIR BROKEN MANUFACTURED WIRE CONNECTORS END DOORS COUNTER.
17.) FINISH BOLDING DISCONNECT ENCLOUSER AT RADIAL ARM SAW
18.) SUPPORT SEALTITE AT PANEL SAW.
19.) INSTALL DUST CAP TAP BOX CUSTOMER SERVICE AREAS UP FRONT.
20.) FINISH TILE CUTTER INSTALLATION.
21.) SUPPORT DATA CONDUITS AS PER CODE.
RECEIVED 255.00 CASH FOR AFTER HOURS INSPECTION AS INSTRUCTED BY RAY MAJUTA
11/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PREVIOUS INSPECTIONS COMPLETED.
1.) FINISH SENSORMATIC
2.) FINISH MOVING EXIT LIGHTING

OK TEMP C OF O FOR STOCKING.
11/22/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK 1.) PLEASE FINISH SENSOR MATIC.
2.) PLEASE PROVIDE INFORMATION REQUESTED FOR DOCK LEVER.
11/20/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) FINISH PREVIOUS INSPECTION.
11/19/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/18/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. VERIFY DOOR CLOSURE LISTING, DOCK LEVELER 2.) EXTENDER RINGS STILL NEEDED. FINISH SENSORMATIC, POWER TO NORTH GARDEN DOORS.
11/15/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO TILE CEILING ROOF OK.
11/14/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SUPPORT CONDUIT ABOVE CEILING. OK MONEY ROOM & MANGER ROOM.
11/13/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
1.) PLEASE PROTECT SEALTTIE FROM SHARP EDGES WHERE PASSING THROUGH UNIT AND TIGHTEN FITTINGS.
2.) PROVIDE SHEILDS TO PANEL BOTTOMS TO SEAL OPENINGS 3.) ILLUMINATION IS NEEDED FOR PANEL SNEF 4,( DOOR NOT TO CLOSE ON ANY PERSONAL WORKING ON ELECTRIC EQUIPMENT.
5.) USE LUG FOR SIZED CONDUCTORS AS APPROVED.
11/12/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE VERIFY GENERTORS AUXILAVARY 150 A DISCONNECT IS LISTED UNDER MANFACTURES LABELING. WE HAVE A BONDING CONCERN AT THIS DISCONNECT PER 250-97.
2.) FINISH MGR OFFICE & ROOM LIGHTING
3.) ATTACH SUPPORT WIRES AT BOTH ENDS 300-11
4.) WHERE MORE THAN 1/4" BETWEEN DEVICES & BOX AN EXTENDER RING IS NEEDED. PLEASE USE AN APPROVED RING. METAL ARE NOT APPROVED.
5.) FINISH WIRING LIGHTING IN GARDEN AREA.
6.) LIGHTING IN GARDEN AREA TO MEET LIGHTING CODES.
7.) M/C CABLE TO TERMANATE IN A FITTING WHEN USED WITH CONDUIT WIRING SYSTEM CHECK ROOF
10/22/2002 ELECTRIC - FINAL Not ready for Inspection SENT TO TEP ON 10/23/02 AT 9:15AM