Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM01844
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
11/18/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
11/15/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
11/14/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
11/13/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
11/12/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
11/07/2002 | ELECTRIC - ABOVE CEILING | Denied | 1)SUPPORT ELECTRIC INDEPENDANTLY OF CEILING WIRES AS PER CODE, ALSO ATTACH AT BOTH ENDS 300-11 2)PLEASE USE FIXTURE CLIPS AS LISTED FOR USE WITH TYPE GRID SYSTEM 410-16(C) 3)SUPPORT M/C CABLE AS PER CODE 334-10 |
|
10/09/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
09/09/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* |