Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM01844
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
11/08/2002 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
10/31/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 4 POLE BASES AS MARKED 1.) LEFT PAPER WORK FOR TEMP C OF O. | |
10/18/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TEMP POWER FOR TEST 1.) POWER OK TO ENERGIZE TO MAIN BREAKERS OF ALL SUB PANELS ELECTRICAL CONTRACTOR RESPONSABLE FOR ANY BRANCH CIRCUITS THAT ARE ENERGIZED. PLEASE CALL FOR INSPECTIONS FOR BRANCH CIRCUITS. | |
10/17/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PLEASE PROVIDE LETTER VERIFING TORQUE OF EQUIPMENT AND CONDUCTORS 2.) BOND FLEX CONDUITS AND TIGHTEN FITTINGS 3.) WE HAVE MUTIPOLE TERMANATIONS AT LUG IN TRANSFORMER 4.) FINISH GROUNDING ELECTRODE CONDUCTOR FOR TANSFORMERS. | |
10/16/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
09/24/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK POLE BASES AS MARKED. | |
09/13/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS OFFICE AND CLASSROOMS AND BATHROOMS. | |
09/09/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK CONDUITS ALONG MAIN RUN FROM PANEL OUT 100' NORTH TO SOUTH COL #M TO H. WEST TO EAST 70' COL #7 TO 5. |